LV ampacity: NEC 2023 Table 310.16 (raceway/cable/earth) and 310.17 (free air); CEC Tables 1–4.
The two sets have been harmonized since 2012 but remain independently published — check both if cross-referencing.
LV underground: CEC uses CSA C22.1:21 Appendix D, Tables D8A–D11B (Diagrams D8–D11).
NEC uses Informative Annex B, Table B.2(10) Details 9/10 (directly buried) and Table B.2(7) Details 1–3
(duct bank). Annex B is informative; the mandatory NEC basis is Table 310.16.
MV ampacity: NEC 2023 Tables 315.60(C)(1)–(20) — the complete set covering single conductors,
triplexed assemblies, and three-conductor cable, installed in free air, in conduit in air, in underground
ducts, or directly buried. Ampacities assume shields grounded at one point. Only single conductors isolated
in air are tabulated above 35 kV.
Termination temperature: CEC Rule 4-006 / NEC 110.14(C) — the usable column is set by the
lowest-rated termination in the circuit.
Bonding / EGC: CEC Table 16; NEC Table 250.122.
Voltage drop: CEC Rule 8-102 with Appendix D Table D3; NEC Chapter 9 impedance data.
Overcurrent protection: CEC Rule 14-104 with Table 13; NEC 240.4(B) and 240.6(A).